Dr Hasan Shariq H.Shariq@hull.ac.uk
Lecturer, School of Engineering
Improving Thermal Performance of Buildings using Smart Inspections and Peltier-driven Heat Recovery
Shariq, Muhammad Hasan
Authors
Contributors
Ben Hughes
Supervisor
Professor Ron Patton R.J.Patton@hull.ac.uk
Supervisor
Abstract
Buildings account for 40% of overall carbon emissions in the UK which have significant impacts on the environment. The overconsumption of energy for heating and cooling is primarily caused by thermal leakages due to building defects. Existing techniques of building façade inspections are often manual, time-consuming and/or labour-intensive, while retrofit techniques like evaporative cooling windcatchers, PCMs, and Earth-to-air Heat Exchangers (EAHE) present massive installation and maintenance challenges.
This study first qualitatively investigates a smart building inspection framework using a novel instantaneous thermal-visible image fusion technique. The data capture results showed pixel-level accuracy invariant to parallax errors. The fused thermal-visible imagery was further evaluated using a self-supervised machine-learning model with pre-trained pseudo labels for defects. The results showed promising fault identification capabilities thanks to the collective visible-thermal information in each dataset.
The primary focus of this research is a detailed quantitative examination of the proposed Peltier-driven cooling mechanism designed for integration with a passive wind tower. This thermoelectric cooling (TEC) system uses heat pipes to rapidly absorb ambient heat through conduction, cooling the air as it passes through multiple layers of actively cooled pipes via convection. The cooling performance was examined and validated through CFD modelling and a full-scale prototype of the cooling unit.
Preliminary results showed a 3.66°C air temperature drop at a 50L/s airflow rate. Three augmentation techniques were proposed: a regulated damper before the cooler, an additional layer of cooling pipes, and an axial fan system to ensure necessary ventilation. In an adiabatic room model of 3m x 2.5m x 2.5m with the proposed TEC cooling through a wind tower, results showed up to 6°C of indoor cooling using the damper before the cooler and up to 8°C of cooling using all three optimisations in combination. This was achieved while maintaining a minimum ventilation rate of 47.9 L/s regardless of external wind speeds. This solar-compatible system promises a large-scale potential to reduce building HVAC loads.
Citation
Shariq, M. H. Improving Thermal Performance of Buildings using Smart Inspections and Peltier-driven Heat Recovery. (Thesis). University of Hull. https://hull-repository.worktribe.com/output/4860398
Thesis Type | Thesis |
---|---|
Deposit Date | Oct 3, 2024 |
Publicly Available Date | Oct 4, 2024 |
Public URL | https://hull-repository.worktribe.com/output/4860398 |
Additional Information | Faculty of Science and Engineering University of Hull |
Award Date | Jul 24, 2024 |
Files
Thesis
(10.8 Mb)
PDF
Publisher Licence URL
http://creativecommons.org/licenses/by/4.0
Copyright Statement
Creative Commons Licence: Attribution 4.0 International License. See: https://creativecommons.org/licenses/by/4.0/
You might also like
Low power energy harvesting systems: State of the art and future challenges
(2021)
Journal Article
Urban road and pavement solar collector system for heat island mitigation: Assessing the beneficial impact on outdoor temperature
(2020)
Presentation / Conference Contribution
Downloadable Citations
About Repository@Hull
Administrator e-mail: repository@hull.ac.uk
This application uses the following open-source libraries:
SheetJS Community Edition
Apache License Version 2.0 (http://www.apache.org/licenses/)
PDF.js
Apache License Version 2.0 (http://www.apache.org/licenses/)
Font Awesome
SIL OFL 1.1 (http://scripts.sil.org/OFL)
MIT License (http://opensource.org/licenses/mit-license.html)
CC BY 3.0 ( http://creativecommons.org/licenses/by/3.0/)
Powered by Worktribe © 2024
Advanced Search